Leave Your Message

Intelligent wireless automatic gas fire extinguishing device-Hot Aerosol Series

Our automatic gas fire extinguishing devices provide comprehensive protection against electrical fires. These intelligent devices monitor wire temperature, ambient temperature, and smoke in real-time. Featuring multiple communication options (RS485, 4G, Lora), these automatic gas fire extinguishing devices enable wireless data upload to cloud platforms for remote monitoring and control via computer or mobile app. With a modular design for easy cartridge replacement, our automatic gas fire extinguishing devices, including the MR/QRR and MR/YF Hot Aerosol series, offer reliable, cost-effective solutions for various protected spaces.

    Type Designation

    QRR Model Difinition
    Model Communication Method Key Features Ideal For
    MR/QRR□G/S-KEG1 Standalone All-in-one unit with integrated detection & extinguishing. No external communication. Basic protection for small, self-contained spaces.
    MR/QRR□G/S-KEG2 RS485 Wired Can be integrated into a central fire alarm control panel for centralized monitoring. Buildings or facilities requiring a centralized wired monitoring system.
    MR/QRR□G/S-KEG3 LORA Wireless Long-range wireless communication. Flexible installation with low network setup cost. Areas with distributed layouts or where wiring is difficult.
    MR/QRR□G/S-KEG4 4G Wireless Connects directly to the cloud platform. Supports remote monitoring and control via mobile app. Multi-site or cross-regional facilities requiring remote, centralized management.

     product Display

    MR QRR0
    MR QRR0

    Product features

    Simultaneous online detection of wire temperature, ambient temperature,and smoke to prevent electrical fire hazards.
    Equipped with various communication interfaces such as RS485, 4G, and Lora.
    Wireless data upload to the cloud platform enables viewing of on-site data and remote control via computer or mobile app from any location.
    Functions include real-time data collection, historical curves, event recording, and trend analysis.
    Two-segment modular product design allows easy replacement of the extinguishing cartridge after use, enabling repeated use and reducing operational costs.

    Technical Parameters

    Function configuration MR/QRR □ G/S-KEG1 MR/QRR □ G/S-KEG2 MR/QRR □ G/S-KEG3 MR/QRR □ G/S-KEG4
    Communication Method / RS485 LORA/433MHz 4G
    Dimensions 0.1G/S:66*45*90mm
    0.3G/S:66*45*255mm
    0.1G/S:66*45*170mm
    0.3G/S:66*45*335mm
    0.1G/S:66*45*170mm
    0.3G/S:66*45*335mm
    0.1G/S:66*45*170mm
    0.3G/S:66*45*335mm
    Operating Voltage / DC24V
    Agent Quantity 0.1G/S:100g±2g
    0.3G/S:300g±2g
    Protected Space 0.1G/S:≤1m³
    0.3G/S:≤3m³
    Discharge Time ≤14s
    Discharge Delay Time ≤0.5s
    Nozzle Thermal Clearance Temperature at 400mm from nozzle ≤75℃
    Surface Temperature of Enclosure ≤75
    Extinguishing Density 100g/m³~130g/m³
    Agent Service Life 6 Years
    Protected Area Requirements Protected area should be relatively enclosed
    Installation Method 3M adhesive, strong magnetic adsorption, screw fixation
    Operating Environment -40~+85  95%RH
    Activation Method Temperature-based activation:
     (when any point of thermal detection line exceeds 170℃)
    Logical activation (temperature exceeds 100℃ and smoke detected simultaneously)
    Remote activation (via host or cloud platform)
    Manual forced start (emergency button, press and hold for 3 seconds)
    Over-temperature activation (when any point of thermal detection line exceeds 170℃)